Waste Heat and Mass Recovery from Boiler Exhaust Gases in a New Generation District Heating System: Energy and Exergy Analysis

MakaleYalnız künye
  • SDG 7 · Erişilebilir ve Temiz Enerji
  • SDG 12 · Sorumlu Üretim ve Tüketim
  • SDG 13 · İklim Eylemi

Özet

The study performs energy and exergy analyses for each component such as boilers, buildings, distribution networks and heat exchangers of a new generation district heating system. Energy and exergy efficiencies are compared for all system components, and energy and exergy losses are presented using Sankey and Grassman diagrams. Three flue gas condensers with finned bundles are designed for different capacities of boilers that intend to recover water and heat from the waste flue gas in the district heating system due to high flue gas energy losses. Colburn-Hougen and one-dimensional finite difference methods are used to design the flue gas condensers with the MATLAB program. The exergy analysis showed that the exergy input to the system is lost by 4.52% from the distribution networks, 4.15% from all buildings and 2.18% from the flue gas. In the system, the energy and exergy efficiencies of the boilers are calculated to be 87.23% and 17.32%, respectively, and the heat loss from the flue gas is found to be 12%. The design results show that the values of mass convection coefficient (km) for all flue gas condensers decrease from 0.0706 at the inlet condensation zone to 0.0354 towards the outlet. The total condensation rate and condensation efficiency are found to be 86 kg/h and 60%, respectively, for the 2500 kW boiler.

Anahtar Kelimeler

RDL Kalıcı Bağlantı (PID)
https://rdlopen.rawdatalibrary.net/r/gumushane/12536Resmi atıflarda kullanılan kalıcı adres
DOI
https://doi.org/10.1007/s13369-023-08453-wYayıncı resmi DOI adresi
Tam Kayıt
AlanDeğerDil
dc.contributor.authorTerhan, Meryem
dc.date.accessioned2026-10-22T10:20:14.182506446Z
dc.date.available2026-10-22T10:20:14.182506446Z
dc.date.issued2024
dc.description.abstractThe study performs energy and exergy analyses for each component such as boilers, buildings, distribution networks and heat exchangers of a new generation district heating system. Energy and exergy efficiencies are compared for all system components, and energy and exergy losses are presented using Sankey and Grassman diagrams. Three flue gas condensers with finned bundles are designed for different capacities of boilers that intend to recover water and heat from the waste flue gas in the district heating system due to high flue gas energy losses. Colburn-Hougen and one-dimensional finite difference methods are used to design the flue gas condensers with the MATLAB program. The exergy analysis showed that the exergy input to the system is lost by 4.52% from the distribution networks, 4.15% from all buildings and 2.18% from the flue gas. In the system, the energy and exergy efficiencies of the boilers are calculated to be 87.23% and 17.32%, respectively, and the heat loss from the flue gas is found to be 12%. The design results show that the values of mass convection coefficient (km) for all flue gas condensers decrease from 0.0706 at the inlet condensation zone to 0.0354 towards the outlet. The total condensation rate and condensation efficiency are found to be 86 kg/h and 60%, respectively, for the 2500 kW boiler.
dc.identifier.doi10.1007/s13369-023-08453-w
dc.identifier.eissn2191-4281
dc.identifier.endpage10630
dc.identifier.issn2193-567X
dc.identifier.issue8
dc.identifier.scopus2-s2.0-85176758638
dc.identifier.startpage10613
dc.identifier.urihttps://rdlopen.rawdatalibrary.net/r/gumushane/12536
dc.identifier.volume49
dc.identifier.wosWOS:001102352800001
dc.language.isoen
dc.publisherSpringer Nature
dc.relation.ispartofArabian Journal for Science and Engineering
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.subjectBoiler
dc.subjectEnergy and exergy analysis
dc.subjectFinned flue gas condenser
dc.subjectHeat and Mass recovery
dc.subjectNew generation district heating
dc.subject.classificationMultidisciplinary Sciences
dc.subject.classificationScience & Technology - Other Topics
dc.subject.otherDEW-POINT TEMPERATURES
dc.subject.otherFLUE-GAS
dc.subject.otherFIRED BOILERS
dc.subject.otherECONOMIZER
dc.subject.otherDESIGN
dc.subject.otherPUMP
dc.subject.otherFIN
dc.titleWaste Heat and Mass Recovery from Boiler Exhaust Gases in a New Generation District Heating System: Energy and Exergy Analysis
dc.typeArticle
dspace.entity.typePublication
rdl.citation.openalex3
rdl.citation.scopus3
rdl.citation.wos3
rdl.oa.statusclosed
rdl.sdgSDG07
rdl.sdgSDG13
rdl.sdgSDG12
rdl.source.indexSCOPUS
rdl.source.indexWOS
rdl.wos.indexScience Citation Index Expanded (SCI-EXPANDED)